Rule: Copy Panel Manufacturers to WE Manufacturer and slot bigger than 0 for DCS/CENTUM CS 3000
Rule action: Check data.
Priority: 1(low).
Component 1: Wiring Equipment.
Component 2: Wiring Equipment- Panel.
Filter Information:
-
[Operand1] Wiring Equipment; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And
-
[Operand1] Wiring Equipment; [Property] Panel Manufacturer; [Operator] =; [Operand2] Value; [Property/Value] CENTUM CS 3000; [Logical Operator] And
-
[Operand1] Wiring Equipment; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant
Consistency information:
-
[Operand1] Wiring Equipment; [Property] Wiring Equipment Manufacture; [Copy] <=; [Compare] =; [Operand2] Wiring Equipment - Panel; [Property/Value] Panel Manufacture; [Action] Error
-
[Operand1] Wiring Equipment; [Copy] None; [Compare] Not Empty; [Action] Error
Rule: I/O Card Name must start with C then equal to number
Rule action: Check data.
Priority: 1(low).
Component 1: Wiring Equipment.
Component 2: Wiring Equipment - Panel.
Filter Information:
-
[Operand1] Wiring Equipment; [Property] Wiring Equipment Category; [Operator] =; [Operand2] Value; [Property/Value] I/O Card; [Logical Operator] And
-
[Operand1] Wiring Equipment - Panel; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant; [Logical Operator] And
-
[Operand1] Wiring Equipment - Panel; [Property] Panel Manufacture; [Operator] =; [Operand2] Value; [Property/Value] Emerson Process; [Logical Operator] And
-
[Operand1] Wiring Equipment - Panel; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS
Consistency information:
-
[Operand1] Wiring Equipment; [Property] Wiring Equipment; [Start] 1; [Length] 1; [Copy] None; [Compare] >=; [Operand2] Value; [Property/Value] C; [Action] Error
-
[Operand1] Wiring Equipment; [Property] Wiring Equipment; [Start] 2; [Length] 99; [Copy] None; [Compare] <=; [Operand2] Value; [Property/Value] 01; [Action] Error
Rule: Disables Manufacture; Model; I/O Type; Module; Controller; Name; Type in wiring for DCS/Centum CS 3000
Rule action: Control graphic interface.
Priority: 1(low).
Component 1: Wiring Equipment.
Component 2: Wiring Equipment - Panel.
Filter Information:
-
[Operand1] Wiring Equipment - Panel; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And
-
[Operand1] Wiring Equipment - Panel; [Property] Panel Manufacturer; [Operator] =; [Operand2] Value; [Property/Value] Centum CS 3000; [Logical Operator] And
-
[Operand1] Wiring Equipment - Panel; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant
Consistency information:
-
[Operand1] Wiring Equipment; [Property] Wiring Equipment Manufacture
-
[Operand1] Wiring Equipment; [Property] Wiring Equipment Model
-
[Operand1] Wiring Equipment; [Property] Instrument I/O Type
-
[Operand1] Wiring Equipment; [Property] Wiring Equipment Module
-
[Operand1] Wiring Equipment;
-
[Operand1] Wiring Equipment; [Property] Wiring Equipment
-
[Operand1] Wiring Equipment; [Property] Wiring Equipment Type
Rule: Disables Series; Type; Manufacture; I/O Type; Redundant Flag in Wiring Equipment for DCS/Emerson Process
Rule action: Control graphic interface.
Priority: 1(low).
Component 1: Wiring Equipment.
Component 2: Wiring Equipment - Panel.
Filter Information:
-
[Operand1] Wiring Equipment - Panel; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And
-
[Operand1] Wiring Equipment - Panel; [Property] Panel Manufacturer; [Operator] =; [Operand2] Value; [Property/Value] Emerson Process; [Logical Operator] And
-
[Operand1] Wiring Equipment - Panel; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant
Consistency information:
-
[Operand1] Wiring Equipment; [Property] Series
-
[Operand1] Wiring Equipment; [Property] Wiring Equipment Type
-
[Operand1] Wiring Equipment; [Property] Wiring Equipment Manufacture
-
[Operand1] Wiring Equipment; [Property] Instrument I/O Type
-
[Operand1] Wiring Equipment; [Property] Redundant
This System rule can be found in the Wiring > Disable Properties folder:
Rule: Double Width in Telecom Equipment
Rule action: Control graphic interface.
Priority: 1(low).
Component 1: Wiring Equipment.
Filter Information:
-
[Operand1] Wiring Equipment [Property] Wiring Equipment Category [Operator] =; [Operand 2] Value [Property/Value] Amplifier; [Logical Operator] Or
-
[Operand1] Wiring Equipment [Property] Wiring Equipment Category [Operator] =; [Operand 2] Value [Property/Value] Hub; [Logical Operator] Or
-
[Operand1] Wiring Equipment [Property] Wiring Equipment Category [Operator] =; [Operand 2] Value [Property/Value] Intercom [Logical Operator] Or.
-
[Operand1] Wiring Equipment [Property] Wiring Equipment Category [Operator] =; [Operand 2] Value [Property/Value] Miscellaneous Telecom Equipment [Logical Operator] Or.
-
[Operand1] Wiring Equipment [Property] Wiring Equipment Category [Operator] =; [Operand 2] Value [Property/Value] PA Channel [Logical Operator] Or.
-
[Operand1] Wiring Equipment [Property] Wiring Equipment Category [Operator] =; [Operand 2] Value [Property/Value] Switch [Logical Operator] Or. Consistency information: [Operand1]Wiring Equipment; [Property] Double Width