Component 1 - Instrument - Intergraph Smart Instrumentation - Help

Intergraph Smart Instrumentation Rule Manager Help

Language
English
Product
Intergraph Smart Instrumentation
Search by Category
Help
Smart Instrumentation Version
2018 (12.0)

Rule: Backup Link Master is not Null for DCS/CENTUM CS 3000.

Rule action: Check data.

Priority: 1(low).

Component 1: Instrument.
Component 2: Channel - DCS Panel*.

Filter Information:

  • [Operand1] Channel DCS Panel*; [Property] Panel Category; [Operator] =; [Property/Value] DCS; [Logical Operator] And

  • [Operand1] Channel DCS Panel*; [Property] Panel Manufacturer; [Operator] =; [Property/Value] CENTUM CS 3000; [Logical Operator] And

  • [Operand1] Channel DCS Panel*; [Property] Plant/Reference Panel; [Operator] =; [Property/Value] Plant.

Consistency information: [Operand1] Instrument; [Property] Backup Link Master; [Copy] None; [Compare] In; [Operand2] Value; [Property/Value] Y,N;  [Action] Error.

Rule: Backup Link Master is not Null for DCS/Emerson Process

Rule action: Check data.

Priority: 1(low).

Component 1: Instrument.
Component 2: Channel - DCS Panel*.

Filter Information:

  • [Operand1] Channel DCS Panel*; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And

  • [Operand1] Channel DCS Panel*; [Property] Panel Manufacturer; [Operator] =; [Operand2] Value; [Property/Value] Emerson Process; [Logical Operator] And

  • [Operand1] Channel DCS Panel*; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant

Consistency information: [Operand1] Instrument; [Property] Backup Link Master; [Copy] None; [Compare] In; [Operand2] Value; [Property/Value] Y,N;  [Action] Error.

Rule: Copies Bi-directional Linear Type between Instrument and Control System Type

Rule action: Check data.

Priority: 1(low).

Component 1: Instrument.
Component 2: Control System Tag - Instrument.

Consistency information: [Operand1] Instrument; [Property] Linearity Type; [Copy] <=>; [Compare] =; [Operand2] Control System Tag; [Property/Value] Linearity Type; [Action] Error

Rule: Fieldbus Device Panel Address must be 20 for FF Instr/DCS/Emerson Process/Backup Link Master = Y

Rule action: Check data.

Priority: 1(low).

Component 1: Instrument.
Component 2: Instrument - Channel - DCS Panel*.

Filter Information:

  • [Operand1] Instrument; [Property] Tag Class;  [Operator] =; [Operand2] Value; [Property/Value] Foundation Fieldbus; [Logical Operator] And

  • [Operand1] Instrument - Channel - DCS Panel*; [Property] Panel Category;  [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And

  • [Operand1] Instrument - Channel - DCS Panel*; [Property] Panel Manufacture; [Operator] =; [Operand2] Value; [Property/Value] Emerson Process; [Logical Operator] And

  • [Operand1] Instrument; [Property] Backup Link Master; [Operator] =; [Operand2] Value; [Property/Value] Y; [Logical Operator] And

  • [Operand1] Instrument - Channel - DCS Panel*; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant

Consistency information:

  • [Operand1] Instrument; [Property] Fieldbus Device Panel Address; [Copy] None; [Compare] =; [Operand2] Value; [Property/Value] 20; [Action] Error

Rule: Fieldbus Device Panel Address must be 20 for Fieldbus Instr/DCS/Centum CS 3000/Backup Link Master = Y

Rule action: Check data.

Priority: 1(low).

Component 1: Instrument.
Component 2: Instrument - Channel - DCS Panel*.

Filter Information:

  • [Operand1] Instrument; [Property] Tag Class;  [Operator] =; [Operand2] Value; [Property/Value] Foundation Fieldbus; [Logical Operator] And

  • [Operand1] Instrument - Channel - DCS Panel*; [Property] Panel Category;  [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And

  • [Operand1] Instrument - Channel - DCS Panel*; [Property] Panel Manufacture; [Operator] =; [Operand2] Value; [Property/Value] Centum CS 3000; [Logical Operator] And

  • [Operand1] Instrument; [Property] Backup Link Master; [Operator] =; [Operand2] Value; [Property/Value] Y; [Logical Operator] And

  • [Operand1] Instrument - Channel - DCS Panel*; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant

Consistency information:

  • [Operand1] Instrument; [Property] Fieldbus Device Panel Address; [Copy] None; [Compare] =; [Operand2] Value; [Property/Value] 20; [Action] Error

Rule: Fieldbus Device Panel Address must be between 20 and 35 for Fieldbus Instr/DCS/Centum CS 3000

Rule action: Check data.

Priority: 1(low).

Component 1: Instrument.
Component 2: Instrument - Channel - DCS Panel*.

Filter Information:

  • [Operand1] Instrument; [Property] Tag Class;  [Operator] =; [Operand2] Value; [Property/Value] Foundation Fieldbus; [Logical Operator] And

  • [Operand1] Instrument - Channel - DCS Panel*; [Property] Panel Category;  [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And

  • [Operand1] Instrument - Channel - DCS Panel*; [Property] Panel Manufacture; [Operator] =; [Operand2] Value; [Property/Value] Centum CS 3000; [Logical Operator] And

  • [Operand1] Instrument - Channel - DCS Panel*; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant

Consistency information:

  • [Operand1] Instrument; [Property] Fieldbus Device Panel Address; [Copy] None; [Compare] >=; [Operand2] Value; [Property/Value] 20; [Action] Error

  • [Operand1] Instrument; [Property] Fieldbus Device Panel Address; [Copy] None; [Compare] <=; [Operand2] Value; [Property/Value] 35; [Action] Error

Rule: Fieldbus Device Panel Address must be between 20 and 35 for Fieldbus Instrument/DCS/Emerson Process

Rule action: Check data.

Priority: 1(low).

Component 1: Instrument.
Component 2: Instrument - Channel - DCS Panel*.

Filter Information:

  • [Operand1] Instrument; [Property] Tag Class;  [Operator] =; [Operand2] Value; [Property/Value] Foundation Fieldbus; [Logical Operator] And

  • [Operand1] Instrument - Channel - DCS Panel*; [Property] Panel Category;  [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And

  • [Operand1] Instrument - Channel - DCS Panel*; [Property] Panel Manufacture; [Operator] =; [Operand2] Value; [Property/Value] Emerson Process; [Logical Operator] And

  • [Operand1] Instrument - Channel - DCS Panel*; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant

Consistency information:

  • [Operand1] Instrument; [Property] Fieldbus Device Panel Address; [Copy] None; [Compare] >=; [Operand2] Value; [Property/Value] 20; [Action] Error

  • [Operand1] Instrument; [Property] Fieldbus Device Panel Address; [Copy] None; [Compare] <=; [Operand2] Value; [Property/Value] 35; [Action] Error

Rule: Trim Instrument Tag Names

This rule is in the Instrument Index > Consistency folder.

Rule action: Check data.

Priority: 1 (low).

Component 1: Instrument.

Consistency information:

  • [Operand1] Instrument [Property] Instrument Name [Copy] | None [Compare] Custom Update [Operand 2] Assembly [Property/Value] spiTrimTagName.TrimName[Action] Error.