Rule: Backup Link Master is not Null for DCS/CENTUM CS 3000.
Rule action: Check data.
Priority: 1(low).
Component 1: Instrument.
Component 2: Channel - DCS Panel*.
Filter Information:
-
[Operand1] Channel DCS Panel*; [Property] Panel Category; [Operator] =; [Property/Value] DCS; [Logical Operator] And
-
[Operand1] Channel DCS Panel*; [Property] Panel Manufacturer; [Operator] =; [Property/Value] CENTUM CS 3000; [Logical Operator] And
-
[Operand1] Channel DCS Panel*; [Property] Plant/Reference Panel; [Operator] =; [Property/Value] Plant.
Consistency information: [Operand1] Instrument; [Property] Backup Link Master; [Copy] None; [Compare] In; [Operand2] Value; [Property/Value] Y,N; [Action] Error.
Rule: Backup Link Master is not Null for DCS/Emerson Process
Rule action: Check data.
Priority: 1(low).
Component 1: Instrument.
Component 2: Channel - DCS Panel*.
Filter Information:
-
[Operand1] Channel DCS Panel*; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And
-
[Operand1] Channel DCS Panel*; [Property] Panel Manufacturer; [Operator] =; [Operand2] Value; [Property/Value] Emerson Process; [Logical Operator] And
-
[Operand1] Channel DCS Panel*; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant
Consistency information: [Operand1] Instrument; [Property] Backup Link Master; [Copy] None; [Compare] In; [Operand2] Value; [Property/Value] Y,N; [Action] Error.
Rule: Copies Bi-directional Linear Type between Instrument and Control System Type
Rule action: Check data.
Priority: 1(low).
Component 1: Instrument.
Component 2: Control System Tag - Instrument.
Consistency information: [Operand1] Instrument; [Property] Linearity Type; [Copy] <=>; [Compare] =; [Operand2] Control System Tag; [Property/Value] Linearity Type; [Action] Error
Rule: Fieldbus Device Panel Address must be 20 for FF Instr/DCS/Emerson Process/Backup Link Master = Y
Rule action: Check data.
Priority: 1(low).
Component 1: Instrument.
Component 2: Instrument - Channel - DCS Panel*.
Filter Information:
-
[Operand1] Instrument; [Property] Tag Class; [Operator] =; [Operand2] Value; [Property/Value] Foundation Fieldbus; [Logical Operator] And
-
[Operand1] Instrument - Channel - DCS Panel*; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And
-
[Operand1] Instrument - Channel - DCS Panel*; [Property] Panel Manufacture; [Operator] =; [Operand2] Value; [Property/Value] Emerson Process; [Logical Operator] And
-
[Operand1] Instrument; [Property] Backup Link Master; [Operator] =; [Operand2] Value; [Property/Value] Y; [Logical Operator] And
-
[Operand1] Instrument - Channel - DCS Panel*; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant
Consistency information:
-
[Operand1] Instrument; [Property] Fieldbus Device Panel Address; [Copy] None; [Compare] =; [Operand2] Value; [Property/Value] 20; [Action] Error
Rule: Fieldbus Device Panel Address must be 20 for Fieldbus Instr/DCS/Centum CS 3000/Backup Link Master = Y
Rule action: Check data.
Priority: 1(low).
Component 1: Instrument.
Component 2: Instrument - Channel - DCS Panel*.
Filter Information:
-
[Operand1] Instrument; [Property] Tag Class; [Operator] =; [Operand2] Value; [Property/Value] Foundation Fieldbus; [Logical Operator] And
-
[Operand1] Instrument - Channel - DCS Panel*; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And
-
[Operand1] Instrument - Channel - DCS Panel*; [Property] Panel Manufacture; [Operator] =; [Operand2] Value; [Property/Value] Centum CS 3000; [Logical Operator] And
-
[Operand1] Instrument; [Property] Backup Link Master; [Operator] =; [Operand2] Value; [Property/Value] Y; [Logical Operator] And
-
[Operand1] Instrument - Channel - DCS Panel*; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant
Consistency information:
-
[Operand1] Instrument; [Property] Fieldbus Device Panel Address; [Copy] None; [Compare] =; [Operand2] Value; [Property/Value] 20; [Action] Error
Rule: Fieldbus Device Panel Address must be between 20 and 35 for Fieldbus Instr/DCS/Centum CS 3000
Rule action: Check data.
Priority: 1(low).
Component 1: Instrument.
Component 2: Instrument - Channel - DCS Panel*.
Filter Information:
-
[Operand1] Instrument; [Property] Tag Class; [Operator] =; [Operand2] Value; [Property/Value] Foundation Fieldbus; [Logical Operator] And
-
[Operand1] Instrument - Channel - DCS Panel*; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And
-
[Operand1] Instrument - Channel - DCS Panel*; [Property] Panel Manufacture; [Operator] =; [Operand2] Value; [Property/Value] Centum CS 3000; [Logical Operator] And
-
[Operand1] Instrument - Channel - DCS Panel*; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant
Consistency information:
-
[Operand1] Instrument; [Property] Fieldbus Device Panel Address; [Copy] None; [Compare] >=; [Operand2] Value; [Property/Value] 20; [Action] Error
-
[Operand1] Instrument; [Property] Fieldbus Device Panel Address; [Copy] None; [Compare] <=; [Operand2] Value; [Property/Value] 35; [Action] Error
Rule: Fieldbus Device Panel Address must be between 20 and 35 for Fieldbus Instrument/DCS/Emerson Process
Rule action: Check data.
Priority: 1(low).
Component 1: Instrument.
Component 2: Instrument - Channel - DCS Panel*.
Filter Information:
-
[Operand1] Instrument; [Property] Tag Class; [Operator] =; [Operand2] Value; [Property/Value] Foundation Fieldbus; [Logical Operator] And
-
[Operand1] Instrument - Channel - DCS Panel*; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And
-
[Operand1] Instrument - Channel - DCS Panel*; [Property] Panel Manufacture; [Operator] =; [Operand2] Value; [Property/Value] Emerson Process; [Logical Operator] And
-
[Operand1] Instrument - Channel - DCS Panel*; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant
Consistency information:
-
[Operand1] Instrument; [Property] Fieldbus Device Panel Address; [Copy] None; [Compare] >=; [Operand2] Value; [Property/Value] 20; [Action] Error
-
[Operand1] Instrument; [Property] Fieldbus Device Panel Address; [Copy] None; [Compare] <=; [Operand2] Value; [Property/Value] 35; [Action] Error
The following rule can be found in the Instrument Index > Consistency folder:
Rule: Trim Instrument Tag Names
Rule action: Check data.
Priority: 1 (low).
Component 1: Instrument.
Consistency information:
-
[Operand1] Instrument [Property] Instrument Name [Copy] | None [Compare] Custom Update [Operand 2] Assembly [Property/Value] spiTrimTagName.TrimName[Action] Error.