Calculate internal pipe diameter at flow temperature:
-
Calculate correction factor for steam quality (for liquid, water, and gas FS=1);
-
Calculate orifice diameter at flow temperature.
-
For Lo-Loss tube, nozzles,and Venturi tubes:
-
For other orifices:
-
-
Calculate b ratio.
-
For all Flow meters except Segmental orifices:
-
Segmental orifices.
-
Calculate segmental radius:
-
Calculate b ratio.
HS is calculated with the help of HS0 in accordance with step 3b.
-
-
-
Calculate gas expansion factor (for liquid and water, EPS=1).
-
For square edge orifice with 2½D and 8D pipe taps:
-
For Lo-Loss tube, nozzles,and Venturi tubes:
-
For eccentric orifices:
-
For square-edge orifices specified in ISO 5167-2003 (flange tappings, corner tappings, and radius tappings):
-
For other Flow meters:
-
-
Calculate first estimate for flow rate:
*W0 [kg/s]
-
Calculate Pipe Reynolds number:
*W0 [kg/s]
-
Calculate discharge coefficient.For more information see the Appendix.
-
Calculate new flow rate:
*W[kg/s]
-
For quarter of circle (Quadrant Edge) orifice, Lo-loss tube, Venturi tubes, and Segmental orifices go to step 13.
-
Calculate the relative change in Flow rate:
-
Repeat steps 7 to 11 until the relative change in the flow rate is less than 0.0001.
-
For quarter of circle (Quadrant Edge) orifice, calculate radius of upstream profile: