Calculate internal pipe diameter at flow temperature:
-
Calculate correction factor for steam quality. (For liquid, water, and gas, Fs=1):
-
Calculate scale reading factor:
-
Calculate differential pressure at normal flow rate:
-
Calculate Pipe Reynolds number at normal flow rate:
-
Calculate first estimate for b ratio:
-
For Venturi tubes:
-
For other Flow meters:
-
-
Calculate gas expansion factor (for liquid and water, Eps = 1).
-
For square-edge orifice with 21/2D and 8D pipe taps:
-
For Lo-Loss tubes, Venturi tubes and nozzles:
-
For eccentric orifices:
-
For square-edge orifices specified in ISO 5167-2003 (flange tappings, corner tappings, and radius tappings):
-
For other Flow meters:
-
-
Calculate discharge coefficient.For more information see the Appendix.
-
Calculate new b - ratio
-
Calculate the relative change in b - ratio.
-
Repeat steps 7 to 10 until the relative change in the b -ratio is less than 0.0001.
-
Calculate orifice diameter at flow temperature:
-
For all Flow meters except Segmental orifices:
-
Segmental orifices:
-
Calculate Segmental radius:
-
Calculate Segmental height at flow temperature using the equation:
-
For further calculation of Segmental orifices, HS and HS0 are analogous to d and d0 respectivly.
-
-
Calculate orifice diameter at ambient temperature:
-
For Lo-Loss tube, nozzles and Venturi tubes:
-
For other orifices:
-
-
For quarter of circle (Quadrant Edge) orifice, calculate radius