SmartPlant Instrumentation Rule Manager is supplied with a set of rules. These rules consist of:
Engineering
Rules that can be modified by the user. By default these rules are disabled (except for the KKS Cable Name rule). To activate, the user must clear the Disable Rule check box on the General tab of the Rule Properties dialog box of each required rule.
System
Rules that cannot be altered by the user, and are active within SmartPlant Instrumentation at all times, even if Rule Manager has not been selected in the Domain features of the Domain Definition in the SmartPlant System Administration module, to operate.
These Engineering rules can be found in the Interfaces folder:
Rule: Backup Link Master is not Null for DCS/CENTUM CS 3000.
Rule action: Check data.
Priority: 1(low).
Component 1: Instrument.
Component 2: Channel - DCS Panel*.
Filter Information:
-
[Operand1] Channel DCS Panel*; [Property] Panel Category; [Operator] =; [Property/Value] DCS; [Logical Operator] And
-
[Operand1] Channel DCS Panel*; [Property] Panel Manufacturer; [Operator] =; [Property/Value] CENTUM CS 3000; [Logical Operator] And
-
[Operand1] Channel DCS Panel*; [Property] Plant/Reference Panel; [Operator] =; [Property/Value] Plant.
Consistency information: [Operand1] Instrument; [Property] Backup Link Master; [Copy] None; [Compare] In; [Operand2] Value; [Property/Value] Y,N; [Action] Error.
Rule: Backup Link Master is not Null for DCS/Emerson Process
Rule action: Check data.
Priority: 1(low).
Component 1: Instrument.
Component 2: Channel - DCS Panel*.
Filter Information:
-
[Operand1] Channel DCS Panel*; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And
-
[Operand1] Channel DCS Panel*; [Property] Panel Manufacturer; [Operator] =; [Operand2] Value; [Property/Value] Emerson Process; [Logical Operator] And
-
[Operand1] Channel DCS Panel*; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant
Consistency information: [Operand1] Instrument; [Property] Backup Link Master; [Copy] None; [Compare] In; [Operand2] Value; [Property/Value] Y,N; [Action] Error.
Rule: Both Control System Tag Descriptions Length must be 12 or less for DCS/CENTUM CS 3000
Rule action: Check data.
Priority: 1(low).
Component 1: Control System Tag.
Component 2: Control System Tag - Panel.
Filter Information:
-
[Operand1] Control System Tag - Panel; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS [Logical Operator] And
-
[Operand1] Control System Tag - Panel; [Property] Panel Manufacturer; [Operator] =; [Operand2] Value; [Property/Value] CENTUM CS 3000; [Logical Operator] And
-
[Operand1] Control System Tag - Panel; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant
Consistency information:
-
[Operand1] Control System Tag; [Property] Control System Tag Description; [Function] Length; [Copy] None; [Compare] <=; [Operand2] Value; [Property/Value] 12; [Action] Error
-
[Operand1] Control System Tag; [Property] Control System Tag Description 2; [Function] Length; [Copy] None; [Compare] <=; [Operand2] Value; [Property/Value] 12; [Action] Error
Rule: Both Channel Name Equals Channel Sequence and between 1-8 or 16-32 for DCS/CENTUM CS 3000
Rule action: Check data.
Priority: 1(low).
Component 1: Channel.
Component 2: Channel - Panel.
Filter Information:
-
[Operand1] Channel Panel; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS [Logical Operator] And
-
[Operand1] Channel Panel; [Property] Panel Manufacturer; [Operator] =; [Operand2] Value; [Property/Value] CENTUM CS 3000; [Logical Operator] And
-
[Operand1] Channel Panel; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant
Consistency information:
-
[Operand1] Channel; [Property] Channel; [Copy] None; [Compare] =; [Operand2] Channel; [Property/Value] Channel Sequence; [Action] Error
-
[Operand1] Channel; [Property] Channel Sequence; [Copy] None; [Compare] IN; [Operand2] Value; [Property/Value] 1, 2, 3, 4, 5, 6, 7, 8, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32; [Action] Error
Rule: Control Strategy Document Number must be equal to 1 or more for DCS/CENTUM CS 3000
Rule action: Check data.
Priority: 1(low).
Component 1: Control System Tag.
Component 2: Control System Tag - Panel.
Filter Information:
-
[Operand1] Control System Tag - Panel; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS [Logical Operator] And
-
[Operand1] Control System Tag - Panel; [Property] Panel Manufacturer; [Operator] =; [Operand2] Value; [Property/Value] CENTUM CS 3000; [Logical Operator] And
-
[Operand1] Control System Tag - Panel; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant
Consistency information: [Operand1] Control System Tag; [Property] Control Strategy Document Number; [Copy] None; [Compare] >=; [Operand2] Value; [Property/Value] 1; [Action] Error
Rule: Controller is Unique for Domain
Rule action: Check data.
Priority: 1(low).
Component 1: Controller.
Consistency information: [Operand1] Controller; [Property] Controller; [Copy] None; [Compare] Unique; [Operand2]Controller; [Property/Value] Controller; [Action] Error
Rule: Controller Name Upper Case and Maximum 16 Chars.
Rule action: Check data.
Priority: 1(low).
Component 1: Controller.
Consistency information:
-
[Operand1] Controller; [Property] Controller; [Function] Upper; [Copy] None; [Compare] =; [Operand2]Controller; [Property/Value] Controller; [Action] Warning
-
[Operand1] Controller; [Property] Controller; [Function] Length; [Copy] None; [Compare] <=; [Operand2]Controller; [Property/Value] 16; [Action] Warning
Rule: Copies Bi-directional Linear Type between Instrument and Control System Type
Rule action: Check data.
Priority: 1(low).
Component 1: Instrument.
Component 2: Control System Tag - Instrument.
Consistency information: [Operand1] Instrument; [Property] Linearity Type; [Copy] <=>; [Compare] =; [Operand2] Control System Tag; [Property/Value] Linearity Type; [Action] Error
Rule: Copy Instrument Function to Control System Tag Function for Virtual Instrument
Rule action: Check data.
Priority: 1(low).
Component 1: Control System Tag.
Component 2: Control System Tag - Instrument.
Filter Information: [Operand1] Control System Tag - Instrument; [Property] Tag Class; [Operator] =; [Operand2] Value; [Property/Value] Foundation/Profibus PA virtual tag
Consistency information: [Operand1] Control System Tag - Panel; [Property] DCS Function Block Type; [Copy] <=; [Compare] =; [Operand2] Control System Tag - Instrument; [Property/Value] Function; [Action] Error
Rule: Copy Panel Manufacturers to WE Manufacturer and slot bigger than 0 for DCS/CENTUM CS 3000
Rule action: Check data.
Priority: 1(low).
Component 1: Wiring Equipment.
Component 2: Wiring Equipment- Panel.
Filter Information:
-
[Operand1] Wiring Equipment; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And
-
[Operand1] Wiring Equipment; [Property] Panel Manufacturer; [Operator] =; [Operand2] Value; [Property/Value] CENTUM CS 3000; [Logical Operator] And
-
[Operand1] Wiring Equipment; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant
Consistency information:
-
[Operand1] Wiring Equipment; [Property] Wiring Equipment Manufacture; [Copy] <=; [Compare] =; [Operand2] Wiring Equipment - Panel; [Property/Value] Panel Manufacture; [Action] Error
-
[Operand1] Wiring Equipment; [Copy] None; [Compare] Not Empty; [Action] Error
Rule: DCS Function Block Type for Control System Tag must be 16 or less for DCS/CENTUM CS 3000
Rule action: Check data.
Priority: 1(low).
Component 1: Control System Tag.
Component 2: Control System Tag- Panel.
Filter Information:
-
[Operand1] Control System Tag - Panel; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And
-
[Operand1] Control System Tag - Panel; [Property] Panel Manufacturer; [Operator] =; [Operand2] Value; [Property/Value] CENTUM CS 3000; [Logical Operator] And
-
[Operand1] Control System Tag- Panel; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant
Consistency information:
-
[Operand1] Control System Tag; [Property] DCS Function Type; [Function] Length; [Copy] None; [Compare] - <=; [Operand2] Value; [Property/Value] IT; [Action] Error
Rule: Fieldbus Device Panel Address must be 20 for FF Instr/DCS/Emerson Process/Backup Link Master = Y
Rule action: Check data.
Priority: 1(low).
Component 1: Instrument.
Component 2: Instrument - Channel - DCS Panel*.
Filter Information:
-
[Operand1] Instrument; [Property] Tag Class; [Operator] =; [Operand2] Value; [Property/Value] Foundation Fieldbus; [Logical Operator] And
-
[Operand1] Instrument - Channel - DCS Panel*; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And
-
[Operand1] Instrument - Channel - DCS Panel*; [Property] Panel Manufacture; [Operator] =; [Operand2] Value; [Property/Value] Emerson Process; [Logical Operator] And
-
[Operand1] Instrument; [Property] Backup Link Master; [Operator] =; [Operand2] Value; [Property/Value] Y; [Logical Operator] And
-
[Operand1] Instrument - Channel - DCS Panel*; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant
Consistency information:
-
[Operand1] Instrument; [Property] Fieldbus Device Panel Address; [Copy] None; [Compare] =; [Operand2] Value; [Property/Value] 20; [Action] Error
Rule: Fieldbus Device Panel Address must be 20 for Fieldbus Instr/DCS/Centum CS 3000/Backup Link Master = Y
Rule action: Check data.
Priority: 1(low).
Component 1: Instrument.
Component 2: Instrument - Channel - DCS Panel*.
Filter Information:
-
[Operand1] Instrument; [Property] Tag Class; [Operator] =; [Operand2] Value; [Property/Value] Foundation Fieldbus; [Logical Operator] And
-
[Operand1] Instrument - Channel - DCS Panel*; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And
-
[Operand1] Instrument - Channel - DCS Panel*; [Property] Panel Manufacture; [Operator] =; [Operand2] Value; [Property/Value] Centum CS 3000; [Logical Operator] And
-
[Operand1] Instrument; [Property] Backup Link Master; [Operator] =; [Operand2] Value; [Property/Value] Y; [Logical Operator] And
-
[Operand1] Instrument - Channel - DCS Panel*; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant
Consistency information:
-
[Operand1] Instrument; [Property] Fieldbus Device Panel Address; [Copy] None; [Compare] =; [Operand2] Value; [Property/Value] 20; [Action] Error
Rule: Fieldbus Device Panel Address must be between 20 and 35 for Fieldbus Instr/DCS/Centum CS 3000
Rule action: Check data.
Priority: 1(low).
Component 1: Instrument.
Component 2: Instrument - Channel - DCS Panel*.
Filter Information:
-
[Operand1] Instrument; [Property] Tag Class; [Operator] =; [Operand2] Value; [Property/Value] Foundation Fieldbus; [Logical Operator] And
-
[Operand1] Instrument - Channel - DCS Panel*; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And
-
[Operand1] Instrument - Channel - DCS Panel*; [Property] Panel Manufacture; [Operator] =; [Operand2] Value; [Property/Value] Centum CS 3000; [Logical Operator] And
-
[Operand1] Instrument - Channel - DCS Panel*; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant
Consistency information:
-
[Operand1] Instrument; [Property] Fieldbus Device Panel Address; [Copy] None; [Compare] >=; [Operand2] Value; [Property/Value] 20; [Action] Error
-
[Operand1] Instrument; [Property] Fieldbus Device Panel Address; [Copy] None; [Compare] <=; [Operand2] Value; [Property/Value] 35; [Action] Error
Rule: Fieldbus Device Panel Address must be between 20 and 35 for Fieldbus Instrument/DCS/Emerson Process
Rule action: Check data.
Priority: 1(low).
Component 1: Instrument.
Component 2: Instrument - Channel - DCS Panel*.
Filter Information:
-
[Operand1] Instrument; [Property] Tag Class; [Operator] =; [Operand2] Value; [Property/Value] Foundation Fieldbus; [Logical Operator] And
-
[Operand1] Instrument - Channel - DCS Panel*; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And
-
[Operand1] Instrument - Channel - DCS Panel*; [Property] Panel Manufacture; [Operator] =; [Operand2] Value; [Property/Value] Emerson Process; [Logical Operator] And
-
[Operand1] Instrument - Channel - DCS Panel*; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant
Consistency information:
-
[Operand1] Instrument; [Property] Fieldbus Device Panel Address; [Copy] None; [Compare] >=; [Operand2] Value; [Property/Value] 20; [Action] Error
-
[Operand1] Instrument; [Property] Fieldbus Device Panel Address; [Copy] None; [Compare] <=; [Operand2] Value; [Property/Value] 35; [Action] Error
Rule: I/O Card Name must start with C then equal to number
Rule action: Check data.
Priority: 1(low).
Component 1: Wiring Equipment.
Component 2: Wiring Equipment - Panel.
Filter Information:
-
[Operand1] Wiring Equipment; [Property] Wiring Equipment Category; [Operator] =; [Operand2] Value; [Property/Value] I/O Card; [Logical Operator] And
-
[Operand1] Wiring Equipment - Panel; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant; [Logical Operator] And
-
[Operand1] Wiring Equipment - Panel; [Property] Panel Manufacture; [Operator] =; [Operand2] Value; [Property/Value] Emerson Process; [Logical Operator] And
-
[Operand1] Wiring Equipment - Panel; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS
Consistency information:
-
[Operand1] Wiring Equipment; [Property] Wiring Equipment; [Start] 1; [Length] 1; [Copy] None; [Compare] >=; [Operand2] Value; [Property/Value] C; [Action] Error
-
[Operand1] Wiring Equipment; [Property] Wiring Equipment; [Start] 2; [Length] 99; [Copy] None; [Compare] <=; [Operand2] Value; [Property/Value] 01; [Action] Error
Rule: Panel Name must start with FCS then [01-31] then [01-64] for DCS/Centum CS 3000
Rule action: Check data.
Priority: 1(low).
Component 1: Panel.
Filter Information:
-
[Operand1] Panel; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And
-
[Operand1] Panel; [Property] Panel Manufacture; [Operator] =; [Operand2] Value; [Property/Value] Centum CS 3000; [Logical Operator] And
-
[Operand1] Panel; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant
Consistency information:
-
[Operand1] Panel; [Property] Panel; [Function] Substring; [Start] 1; [Length] 3; [Copy] None; [Compare] =; [Operand2] Value; [Property/Value] FCS; [Action] Error
-
[Operand1] Panel; [Property] Panel; [Function] Substring; [Start] 4; [Length] 1; [Copy] None; [Compare] Not Empty; [Action] Error
-
[Operand1] Panel; [Property] Panel; [Function] Substring; [Start] 4; [Length] 2; [Copy] None; [Compare] >=; [Operand2] Value; [Property/Value] 1; [Action] Error
-
[Operand1] Panel; [Property] Panel; [Function] Substring; [Start] 4; [Length] 2; [Copy] None; [Compare] <=; [Operand2] Value; [Property/Value] 31; [Action] Error
-
[Operand1] Panel; [Property] Panel; [Function] Substring; [Start] 6; [Length] 1; [Copy] None; [Compare] Not Empty; [Action] Error
-
[Operand1] Panel; [Property] Panel; [Function] Substring; [Start] 6; [Length] 2; [Copy] None; [Compare] >=; [Operand2] Value; [Property/Value] 1; [Action] Error
-
[Operand1] Panel; [Property] Panel; [Function] Substring; [Start] 6; [Length] 2; [Copy] None; [Compare] <=; [Operand2] Value; [Property/Value] 64; [Action] Error
-
[Operand1] Panel; [Property] Panel; [Function] Length; [Copy] None; [Compare] <=; [Operand2] Value; [Property/Value] 7; [Action] Error
Rule: Rack must be between 1 and 15 for DCS/CENTUM CS 3000
Rule action: Check data.
Priority: 1(low).
Component 1: Rack.
Component 2: Rack - Panel.
Filter Information:
-
[Operand1] Rack - Panel; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And
-
[Operand1] Rack - Panel; [Property] Panel Manufacturer; [Operator] =; [Operand2] Value; [Property/Value] CENTUM CS 3000; [Logical Operator] And
-
[Operand1] Rack - Panel; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant
Consistency information:
-
[Operand1] Rack; [Property] Rack Name; [Copy] None; [Compare] >=; [Operand2] Value; [Property/Value] 1; [Action] Error
-
[Operand1] Rack; [Property] Rack Name; [Copy] None; [Compare] >=; [Operand2] Value; [Property/Value] 15; [Action] Error
Rule: Rack must be equal to 1 or more for DCS/Emerson Process
Rule action: Check data.
Priority: 1(low).
Component 1: Rack.
Component 2: Rack - Panel.
Filter Information:
-
[Operand1] Rack - Panel; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And
-
[Operand1] Rack - Panel; [Property] Panel Manufacturer; [Operator] =; [Operand2] Value; [Property/Value] Emerson Process; [Logical Operator] And
-
[Operand1] Rack - Panel; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant
Consistency information:
-
[Operand1] Rack; [Property] Rack Name; [Copy] None; [Compare] >=; [Operand2] Value; [Property/Value] 1; [Action] Warning
Rule: Slot must be between 1 and 8 for DCS/CENTUM CS 3000
Rule action: Check data.
Priority: 1(low).
Component 1: Slot.
Component 2: Slot - Panel.
Filter Information:
-
[Operand1] Slot - Panel; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And
-
[Operand1] Slot - Panel; [Property] Panel Manufacturer; [Operator] =; [Operand2] Value; [Property/Value] CENTUM CS 3000; [Logical Operator] And
-
[Operand1] Slot - Panel; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant
Consistency information:
-
[Operand1] Slot;[Copy] None; [Compare] >=; [Operand2] Value; [Property/Value] 1; [Action] Error
-
[Operand1] Slot;[Copy] None; [Compare] >=; [Operand2] Value; [Property/Value] 8; [Action] Error
Rule: Slot must be between 1 and 8 for DCS/Emerson Process
Rule action: Check data.
Priority: 1(low).
Component 1: Slot.
Component 2: Slot - Panel.
Filter Information:
-
[Operand1] Slot - Panel; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And
-
[Operand1] Slot - Panel; [Property] Panel Manufacturer; [Operator] =; [Operand2] Value; [Property/Value] Emerson Process; [Logical Operator] And
-
[Operand1] Slot - Panel; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant
Consistency information:
-
[Operand1] Slot; [Copy] None; [Compare] >=; [Operand2] Value; [Property/Value] 1; [Action] Error
-
[Operand1] Slot; [Copy] None; [Compare] >=; [Operand2] Value; [Property/Value] 8; [Action] Error
Rule: Disables Manufacture; Model; I/O Type; Module; Controller; Name; Type in wiring for DCS/Centum CS 3000
Rule action: Control graphic interface.
Priority: 1(low).
Component 1: Wiring Equipment.
Component 2: Wiring Equipment - Panel.
Filter Information:
-
[Operand1] Wiring Equipment - Panel; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And
-
[Operand1] Wiring Equipment - Panel; [Property] Panel Manufacturer; [Operator] =; [Operand2] Value; [Property/Value] Centum CS 3000; [Logical Operator] And
-
[Operand1] Wiring Equipment - Panel; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant
Consistency information:
-
[Operand1] Wiring Equipment; [Property] Wiring Equipment Manufacture
-
[Operand1] Wiring Equipment; [Property] Wiring Equipment Model
-
[Operand1] Wiring Equipment; [Property] Instrument I/O Type
-
[Operand1] Wiring Equipment; [Property] Wiring Equipment Module
-
[Operand1] Wiring Equipment;
-
[Operand1] Wiring Equipment; [Property] Wiring Equipment
-
[Operand1] Wiring Equipment; [Property] Wiring Equipment Type
Rule: Disables Sequence Address in Channel for DCS/Centum CS 3000
Rule action: Control graphic interface.
Priority: 1(low).
Component 1: Channel.
Component 2: Channel - Panel.
Filter Information:
-
[Operand1] Channel - Panel; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And
-
[Operand1] Channel - Panel; [Property] Panel Manufacturer; [Operator] =; [Operand2] Value; [Property/Value] Centum CS 3000; [Logical Operator] And
-
[Operand1] Channel - Panel; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant
Consistency information:
-
[Operand1] Channel; [Property] Channel Sequence
-
[Operand1] Channel; [Property] Address
Rule: Disables Series; Type; Manufacture; I/O Type; Redundant Flag in Wiring Equipment for DCS/Emerson Process
Rule action: Control graphic interface.
Priority: 1(low).
Component 1: Wiring Equipment.
Component 2: Wiring Equipment - Panel.
Filter Information:
-
[Operand1] Wiring Equipment - Panel; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And
-
[Operand1] Wiring Equipment - Panel; [Property] Panel Manufacturer; [Operator] =; [Operand2] Value; [Property/Value] Emerson Process; [Logical Operator] And
-
[Operand1] Wiring Equipment - Panel; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant
Consistency information:
-
[Operand1] Wiring Equipment; [Property] Series
-
[Operand1] Wiring Equipment; [Property] Wiring Equipment Type
-
[Operand1] Wiring Equipment; [Property] Wiring Equipment Manufacture
-
[Operand1] Wiring Equipment; [Property] Instrument I/O Type
-
[Operand1] Wiring Equipment; [Property] Redundant
This System rule can be found in the Wiring > Disable Properties folder:
Rule: Double Width in Telecom Equipment
Rule action: Control graphic interface.
Priority: 1(low).
Component 1: Wiring Equipment.
Filter Information:
-
[Operand1] Wiring Equipment [Property] Wiring Equipment Category [Operator] =; [Operand 2] Value [Property/Value] Amplifier; [Logical Operator] Or
-
[Operand1] Wiring Equipment [Property] Wiring Equipment Category [Operator] =; [Operand 2] Value [Property/Value] Hub; [Logical Operator] Or
-
[Operand1] Wiring Equipment [Property] Wiring Equipment Category [Operator] =; [Operand 2] Value [Property/Value] Intercom [Logical Operator] Or.
-
[Operand1] Wiring Equipment [Property] Wiring Equipment Category [Operator] =; [Operand 2] Value [Property/Value] Miscellaneous Telecom Equipment [Logical Operator] Or.
-
[Operand1] Wiring Equipment [Property] Wiring Equipment Category [Operator] =; [Operand 2] Value [Property/Value] PA Channel [Logical Operator] Or.
-
[Operand1] Wiring Equipment [Property] Wiring Equipment Category [Operator] =; [Operand 2] Value [Property/Value] Switch [Logical Operator] Or. Consistency information: [Operand1]Wiring Equipment; [Property] Double Width
The following rules can be found in the Wiring > Consistency folder:
Rule: Channel Address Should be Unique per I/O Card
Rule action: Check data.
Priority: 1(low).
Component 1: Channel.
Filter Information:
-
[Operand1] Channel [Property] Address [Operator] Not Empty [Logical Operator] AND
-
[Operand1] Channel [Property] Address [Operator] <> [Operand 2] Value [Property/Value] * .
Consistency information:
-
[Operand1] Channel [Property] Address [Copy] | None [Compare] Unique [Operand 2] Channel [Action] Warning.
Rule: KKS Cable Name
Rule action: Check data.
Priority: 1(low).
Component 1: Cable.
Consistency information:
-
[Operand1] Cable [Property] KKS_Application_Area [Copy] | None; [Compare] Custom Update [Operand 2] Assembly [Property/Value] spiKKSCableNum.CableNumbering [Action] Error.
-
[Operand1] Cable [Property] KKS_Cable_Key Sequence [Copy] | None; [Compare] Custom Update [Operand 2] Assembly [Property/Value] spiKKSCableNum.CableNumbering [Action] Error.
-
[Operand1] Cable [Property] KKS_Cable_Key Sequence_Suffix [Copy] | None; [Compare] Custom Update [Operand 2] Assembly [Property/Value] spiKKSCableNum.CableNumbering [Action] Error.
-
[Operand1] Cable [Property] KKS_Function Key [Copy] | None; [Compare] Custom Update [Operand 2] Assembly [Property/Value] spiKKSCableNum.CableNumbering [Action] Error.
-
[Operand1] Cable [Property] Cable Name[Copy] | None; [Compare] Custom Update [Operand 2] Assembly [Property/Value] spiKKSCableNum.CableNumbering [Action] Error.
For the KKS Cable Name rule to function correctly do not remove or modify any of the above parameters. You can add extra lines to the rule whose parameters can be used to define the uniqueness of the KKS cable name.
The following rule can be found in the Instrument Index > Consistency folder:
Rule: Trim Instrument Tag Names
Rule action: Check data.
Priority: 1 (low).
Component 1: Instrument.
Consistency information:
-
[Operand1] Instrument [Property] Instrument Name [Copy] | None [Compare] Custom Update [Operand 2] Assembly [Property/Value] spiTrimTagName.TrimName[Action] Error.