The following, lists and describes the options that you can specify for the multi-sheet and all feeder load summary reports.

Calculation method for All Feeder Load Summary

Allows you to specify the coincidence factor to be used in the calculation of the total connected loads. In Smart Electrical preferences, this option refers to the settings for the Calculation method for All Feeder Load Summary Report. The following options are available:

Use Bus PDB coincidence factor

Uses the coincidence factor of each individual load to calculate the total connected loads on the bus. When calculating the compensated load values, the software multiplies the raw uncompensated load kW and kVAR values by the coincidence factors as defined in the properties of the buses that these loads are connected to. Make sure that you specify these coincidence factors for each bus.

Use each load coincidence factor

Uses the coincidence factors of the PDB bus to calculate the total connected loads on the bus. When calculating the compensated load values, the software multiplies the raw uncompensated load kW and kVAR values by the load coincidence factors.

Coupled buses in All Feeder Load Summary

Allows you to specify inclusion options of coupled buses in the all feeder load summary calculation. In Smart Electrical preferences, this option refers to the settings for the Inclusion of coupled buses in All Feeder Load Summary Report. The following options are available:

Do not include coupled buses

Includes in the calculation only those loads that are connected to the current bus and does not include the loads that are connected on the redundant buses.

Include coupled buses connected by couplers only

Includes in the calculation the loads connected on the current bus as well as loads connected on all the redundant buses that are connected to the current bus by a coupler circuit.

Include coupled buses connected by couplers and bus risers

Includes the loads of the current bus as well as the loads on all the redundant buses that are connected to the current bus by coupler and riser circuits.

Account for converting equipment power losses

Instructs the software to account for converting equipment power losses.

Value type in All Feeder/Multi-Sheet Load Summary reports

Allows you to specify rated or consumed values in All Feeder/Multi-Sheet Load Summary reports.

Rated

Instructs the software to display rated power values in a generated All Feeder/Multi-Sheet Load Summary report.

Consumed

Instructs the software to display consumed power values in a generated All Feeder/Multi-Sheet Load Summary report.

Display Compensated or Uncompensated values in All Feeder/Multi-Sheet Load Summary reports

Allows you to specify compensated or uncompensated values in All Feeder/Multi-Sheet Load Summary reports.

Compensated

Instructs the software to display compensated values in a generated All Feeder/Multi-Sheet Load Summary report.

Uncompensated values

Instructs the software to display uncompensated values in a generated All Feeder/Multi-Sheet Load Summary report.