  • You can generate Enhanced SmartLoop drawings individually or select to generate a number of drawings together in batch mode.

  • When generating Enhanced SmartLoop reports in batch mode, if no generation method has been applied to the selected loops, the software applies the generation method defined in the Smart Instrumentation Preferences dialog, on the page Enhanced Reports > Enhanced SmartLoop > Drawing. The available settings are: By Loop, By Signal, Custom by Loop, and Custom by Signal.

  1. In Smart Instrumentation > Domain Explorer, select one or more loops.

    If among the loops that you selected there are loops assigned to the Manual method (symbol M in the Domain Explorer), the software skips these loops when generating drawings in batch mode.

  2. Right-click and select Reports > Generate Loop Drawings.

  3. On the Generate Loop Drawings dialog, from the Generation method list, select Enhanced Report.

  4. If required, specify the Automatic save options.

  5. Select OK, and at the Report Preview prompt:

    Select Yes to open the print preview of the generated report, to view the report before printing.

    OR

    Select No to start printing the report without viewing.

  • On the General page of the Preferences dialog, you can set the software to display the print preview options: Always, Never or Ask User.

  • The Enhanced Report Utility prints PDFs using Amyuni PDF Converter 5.51 and publishes them to the output folder specified in File > Preferences > Enhanced Reports > <Report Type>> File Locations > Viewer Output Folder field for the specific report type. If no path is present then Amyuni PDF Converter 5.51 publishes the PDF to the Temp folder as specified in File > Preferences > General.