The following procedure explains how to define a neutral earthing connection for a generator by creating a neutral earthing connection branch under a particular generator in the Electrical Engineer.
-
In the Electrical Engineer, under a generator, create an independent branch that starts with a power cable or busway.
-
Right-click an appropriate generator and then select Common Properties on the shortcut menu.
-
Select the Electrical Data tab.
-
Under the Neutral Earthing box, select Find.
-
On the Find dialog, select Find Now and then choose an appropriate child power cable or busway that will be connected to the non-power connection point of the generator symbol in an SLD.
-
Select OK to return to the Electrical Data tab of the Generator Common Properties dialog.
-
Generate an SLD for that generator.
-
After generating an SLD, the diagram will display the neutral earthing branch connected to a non-power connection point of the generator.
-
If you are using custom symbols for your generators in SLDs, make sure that they have an additional non-power connection point. Alternatively, you can use one of the symbol provided in the shipped data.